Download User Manual
Transcript
User Manual – R2485 & System Note: To have Alarm Report and/or Daily Report sent to local PC, switch the Reports ON, then Modem Off Audio Alarm Enable; can be toggled from On to Off; when On, the audible alarm will sound when any alarm occurs. The sound can be silenced by pressing the ENTER button. Audio Alm On Audio Alm Off 5.5.3. Expansion Function Selection & Parameters The enabling/disabling of expansion functions such as AC monitoring, Battery Cell Monitoring and Site Monitoring is described below. These screens form the last screens seen when stepping through the MCSU home Menu. Single Phase AC Monitoring Selection of expansion function 1; when selected, this enables the single phase monitoring screens as well as the screens below. Note that Expansion 1 is not available in 110VDC and 220VDC systems. Expan 1 Expan 1 AC 1-ph High AC voltage threshold; “ACV Hi” alarm will appear when the AC input voltage is higher than this level; the rectifier will switch off independently at some level. It will turn on again when the AC level falls to an appropriate value. Low AC voltage threshold; “ACV Lo” alarm will appear when the AC input voltage is lower than this level; the rectifier will switch off independently at some. It will turn on again when the AC level rises to an appropriate level. none AC V Hi 253V AC V Lo AC frequency high level; this alarm is generated when the AC source frequency is higher than this value; the rectifier does not switch off; AC frequency low level; this alarm is generated when the AC source frequency is lower than this value; the rectifier does not switch off. AC current sensor rating for single phase; the full scale rating of the AC sensor must be entered in this screen. 187V AC Frq Hi 63.0Hz AC Frq Lo 58.0Hz FS AC-I 100A 3 Phase AC Monitoring When the three phase monitoring module is used in the system, the relevant screens are activated by programming to On the 3 Phase AC in Expan 2 section. If programmed to “none” neither the monitoring nor the programmable parameter screens shown below will be displayed. 3 phase AC monitor On or Off can be selected after entering ”Expan 2” sub-menu Allis Electric Co.,Ltd. Expan 2 [ENTER] page 30 of total 82 2002.02