Download User Manual
Transcript
User Manual – R2485 & System 34-way ribbon cable to MiniCSU X18 X1 X28 X17 X40 X31 X32 X39 X22 X2 X180 X23 X33 X34 X44 X45 X50 X64 X65 X179 X129 X115 X103 X89 X76 16-way ribbon cable to MiniCSU Figure 3.9 Figure 3.10 MUIB2 Connection Diagram MUIB2 Connectors Function Conn # Conn Label Class Comments X1 MCSU Anal/Dig 34-way ribbon cable to MCSU X2 USER Digital Relay Contacts; N/O, N/C, Common FAN SPEED Digital Relay Contacts; N/O, N/C, Common HVSD Digital Relay Contacts; N/O, N/C, Common ALARM Digital Relay Contacts; N/O, N/C, Common SMR S/D Digital Relay Contacts; N/O, N/C, Common X17 BAT. TEMP. Analog Temp. Transducer X18 AMB. TEMP. Analog Temp. Transducer X22 C.B. TRIP Digital Aux contact from load CBs X32 1 PHASE AC Anal/Dig 10-way ribbon cable from 1 phase AC monitor module X129 BAT1-Current Analog Batt 1 Current Transducer X115 BAT2-Current Analog Batt 2 Current Transducer X103 BAT3-Current Analog Batt 3 Current Transducer X89 BAT4-Current Analog Batt 4 Current Transducer X23 BAT. SW. Digital Aux contact from Batt. CBs X33 USER 1 Digital User defined input; isolated aux. contact X34 USER 2 Digital Requires special software to define X44 USER3 Digital Requires special software to define X45 USER4 Digital Requires special software to define X28 AN 1 Analog Spare analog I/P - 0 to 5VDC X31 AN 2 Analog Spare analog I/P - 0 to 5VDC X64 LVDS Aux Digital Aux contact from LVDS contactor X65 LVDS Coil Digital Drive for contactor or similar X50 POWER I/P Analog System voltage sensing & DC power input for MCSU X76 LOAD-Current Analog Load Current Transducer X180 MCSU Anal/Dig 16-Way ribbon cable to Aux Port X179 NEXT UNIT Anal/Dig 16-Way ribbon cable to Aux Port Allis Electric Co.,Ltd. page 17 of total 82 2002.02