Reference User Manual AFC Manager ♦ Configuration Tool Liquid and Gas Flow Computer 14.9.3 Why can't the AFC Manager connect to the module? Check the cable used in your project: a null-modem cable should be used to connect the module with the local PC serial port. Make sure that the baud rate, data bits, mode, parity and primary slave address are the same (both in PC and module). If you change the primary slave address and later forget the new address, the module will not establish communications. You must read the primary slave address value (address 100) over the backplane using the Modbus Gateway Transaction Block. 14.9.4 Why do I have to enable or disable a meter? A meter channel will only perform flow calculation if it is enabled. For performance reasons you should disable all meter channels that are not being used. You cannot change a meter type and/or product group for a meter channel that is currently enabled. 14.9.5 Why does the card not calculate results, or why did it stop calculating results? This could be caused by a couple of things. 1 The first thing to check is that the module actually received a clock. If the card does not get a clock it will not be able to schedule storage of historical records. 2 The next possibility is that the meter is not enabled or some parameter for the run is not correct. Check to see if the run is enabled and that no errors exist in configuration or data for the run in question. Check for alarms arising from the calculations. The AFC Manager software can be a great help with this as it will highlight problem areas. 14.9.6 What is the Virtual Modbus Slave? The AFC Modbus database can be accessed using the Primary Modbus Slave address. More than 100.000 registers may be accessed using this slave. You may want to use certain values from the Modbus database in a different order than the one presented in the Primary Modbus Slave. One example is if you want to poll certain values from the Modbus database using a Modbus master device in the field. Instead of using several commands to poll from different locations in the Modbus database, it is better to remap these values to other locations in order to optimize the master polling. This is the reason the AFC module offers a second slave: the Virtual Modbus Slave. Using the AFC Manager software, you can remap up to 20.000 registers from the Primary Modbus Slave in any order. The Virtual Modbus Slave Address must be configured using the AFC Manager software (Site Config dialog box). The Virtual Modbus Slave is also used when using the Modbus Pass-Thru function block. Page 250 of 267 ProSoft Technology, Inc. March 2, 2011