Honeywell • 19
4.1
POWER CABLING
UL standards on cabling
To meet the UL (Underwriters Laboratories) regulations, use a UL-approved copper cable with
a minimum heat-resistance of +140/167°F. Use Class 1 wire only.
The units are suitable for use ona circuit capable of delivering not more than 100,000 rms symmetrical amperes, 600V maximum.
4.1.1
Cable dimensioning and selection
Table 6 shows the minimum dimensions of the Cu/Al-cables and the corresponding fuse sizes.
Recommended fuse types are gG/gL.
If the motor temperature protection of the drive (see Application Manual) is used as an overload
protection, the cable shall be chosen accordingly.
These instructions apply only to cases with one motor and one cable connection from the drive
to the motor. In any other case, ask the factory for more information.