Comissioning settings
Commissioning settings: simultaneously press the + and - buttons for 3 sec.
Legionella prot. B1
No.B4 HWS tank 1
<Leg. protect. off>
Leg. protect. on
Activation of legionella protection.
See options B5 and B6.
Legionella prot. B1
No.B5 HWS tank 1
Legion. protect.
Set-Temperature 70°
Stand:
70°
Adjustment range: 10-75°C
A date and time for running the legionella protection heating program (T=70°C
as set in B5) may be specified with parameter B6. Make sure to choose the
heating period matching the charging times.
Caution: Make sure not to set the temperature level too high, so as to avoid
long heating periods and risk of burning if warm water is let out.
Legionella prot. B1
No.B6 Start-End B1
Mo -- -- -- -- -- -a. 17:00 c.00:00
b. 00:00 d.00:00
No.B7 HWS tank 1
<No dist. pump>
With dist.Heat. 1
You may specify here, if there is a long distance heating pump. However, the
distance heating pump will only work if one of it's associated pumps is running.
No.B11 HWS tank 2
available
< not available >
External pump
Dist. pump
The default setting for this option is "not available" for systems without a
second hot water storage tank. If instead of a second tank an external pump or
long distance heating pump is installed, this has to be specified here.
Parameters B11 or C7 are available for the external pump or long distance
heating pump, depending on which of the outlets is not in use.
on motherboard
Parameters B12 - B17 are not shown, if the "not available" option has been chosen
No.B21 HWS tank 3
available
< not available >
see HWS tank 1
on Extens.module 1
Parameters B22 - B27 are not shown, if the "not available" option has been chosen
No.B31 HWS tank 4
available
< not available >
see HWS tank 1
on Extens.module 1
Parameters B32 - B37 are not shown, if the "not available" option has been chosen
No.B41 HWS tank 5
available
< not available >
see HWS tank 1
on Extens.module 2
Parameters B42 - B47 are not shown, if the "not available" option has been chosen
No.B51 HWS tank 6
available
< not available >
see HWS tank 1
on Extens. Module 2
No.B90 Access all
HWS temp.minimum
On 06:00
Off 22:00
This option is only available, if heating circuit module 1 has been installed. (if
not, a fault will tell you that an extension module is not available)
This option is only available, if heating circuit module 1 has been installed (if
not, a fault will tell you that an extension module is not available)
This option is only available, if heating circuit module 2 has been installed (if
not, a fault will tell you that an extension module is not available)
This option is only available, if heating circuit module 2 has been installed (if
not, a fault will tell you that an extension module is not available)
o
Parameters B52 - B57 are not shown, if the "not available" option has been chosen
If during this time the temperature of the hot water storage falls below a
specified level (default=40°C), it will be charged to that level, regardeless of the
preset time program.