The Fuzzy Control Function Blocks The valencies of the binary input parameters THERM_EL and BIPOLAR have the following effects: THERM_EL BIPOLAR FALSE ( := 2#0) FALSE ( := 2#0) Unipolar voltage or current signal at the input FALSE ( := 2#0) TRUE ( := 2#1) Bipolar voltage or current signal at the input TRUE ( := 2#1) FALSE ( := 2#0) Thermocouple at the input Voltage or Current Signal at the Analog Input Meaning or Effect The function FUZZY_AI normalizes the signal. The function FUZZY_AI normalizes the signal. Normalization is performed in the analog input module. The function only performs an adaptation via the parameters FACTOR and OFFSET. The function FUZZY_AI normalizes the analog input signal in this case to the value range of the relevant input channel of the fuzzy application. The limits MINIMUM and MAXIMUM that define the value range are read from the fuzzy data block. They are processed as limit values in the function. The normalized value is then entered in the fuzzy data block for the respective input. The normalizing value INPUT for bipolar signals is calculated from the respective input value Xi: INPUT + ǒX min Ǔ * (27648–X i) ) X max * (X i ) 27648) * FACTOR ) OFFSET 2 * 27648 The corresponding relationship for unipolar signals is: INPUT + ǒX min Ǔ * (27648–X i) ) X max * X i * FACTOR ) OFFSET 27648 Where: INPUT Xmax Xmin FACTOR OFFSET Xi INPUT Normalized value which is entered in the instance data block Upper limit of the input value range Lower limit of the input value range Factor (gradient) of the normalization lines Offset of the normalization lines at the zero point Value supplied by the analog module Normalization line FACTOR OFFSET Xi Fuzzy Control C79000-G7076-C196-02 3-9 3