Transcript
CALL NOW 800-985-6929 http://www.automatedpt.com Chapter 4 Parameters| Settings Function Description Parameter value 09 programs a Multi-function Input Terminals for external Base Block control. NOTE: When a Base-Block signal is received, the AC motor drive will block all output and the motor will free run. When base block control is deactivated, the AC drive will start its speed search function and synchronize with the motor speed, and then accelerate to Master Frequency. External Base 9 Block (Refer to Pr. 08.06) external base block output frequency Speed searc h starts with last frequency command output voltage synchronous speed detection B.B. time 08.07 speed search 10 UP: Increase Increase/decrease the Master Frequency each time an input is Master Frequency received or continuously when the input stays active. When both inputs are active at the same time, the Master Frequency 11 DOWN: Decrease increase/decrease is halted. Please refer to Pr.02.07, 02.08. This Master Frequency function is also called “motor potentiometer”. Parameter value 12 programs one of the Multi-function Input 12 Counter Trigger Terminals MI3~MI6 (Pr.04.05~Pr.04.08) to increment the AC drive’s internal counter. When an input is received, the counter is incremented by 1. 13 Counter Reset When active, the counter is reset and inhibited. To enable counting the input should be OFF. Refer to Pr.03.05 and 03.06. Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 CALL NOW 800-985-6929 4-91 http://www.automatedpt.com