Chapter 4 Parameters|
Parameter
08.15
Explanation
Factory
Customer
Setting
Settings
Auto Restart After
Fault
0 to 10 (0=disable)
08.16
Auto Reset Time at
Restart after Fault
0.1 to 6000 sec
08.17
Auto Energy Saving
0
60.0
0: Disable
0
1: Enable
0: AVR function enable
08.18
AVR Function
1: AVR function disable
0
2: AVR function disable for decel.
3: AVR function disable for stop
08.19
Software Brake
Level
115V / 230V series: 370.0to 430.0V
380.0
460V series: 740.0 to 860.0V
760.0
0.0~5.0
Compensation
Coefficient for Motor
Instability
0.0
08.21
OOB Sampling Time 0.1 to 120.0 sec
1.0
08.22
Number of OOB
Sampling Times
00 to 32
20
08.23
OOB Average
Sampling Angle
Read only
08.24
DEB Function
08.25
DEB Return Time
0 to 250 sec
08.26
Speed Search
during Start-up
0: Disable
Speed Search
Frequency during
Start-up
0: By setting frequency
08.27
08.20
#.#
0: Disable
0
1: Enable
0
0
1: Enable
1: By max. operation frequency (Pr.01.00)
0
Group 9 Communication Parameters
Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14