CALL NOW 800-985-6929 http://www.automatedpt.com Chapter 4 Parameters| 12.20 AO1 Terminal Analog Signal Mode Factory Setting: 0 Settings 0 AVO1 1 ACO1 (analog current 0.0 to 20.0mA) 2 ACO1 (analog current 4.0 to 20.0mA) Besides parameter setting, the voltage/current mode should be used with the switch. AVI3 AVI4 ACI2 ACI3 12.21 AVO1 AVO2 ACO1 ACO2 AO1 Analog Output Signal Factory Setting: 0 Settings 0 Analog Frequency 1 Analog Current (0 to 250% rated current) This parameter is used to choose analog frequency (0-+10Vdc) or analog current (4-20mA) to correspond to the AC motor drive’s output frequency or current. 12.22 AO1 Analog Output Gain Settings Unit: % 1 to 200% Factory Setting: 100 This parameter is used to set the analog output voltage range. When Pr.12.21 is set to 0, analog output voltage corresponds to the AC motor drive’s output frequency. When Pr.12.22 is set to 100, the max. output frequency (Pr.01.00) setting corresponds to the AFM output (+10VDC or 20mA) When Pr.12.21 is set to 1, analog output voltage corresponds to the AC motor drive’s output current. When Pr.12.22 is set to 100, the 2.5 X rated current corresponds to the AFM output (+10VDC or 20mA) 4-174 Revision Oct. 2009, 07EE, SW--PW V1.14/CTL V2.14 CALL NOW 800-985-6929 http://www.automatedpt.com