Digital Control System
NOT open the direct load command Data Entry Field. Exit the Setup
menu, and then try again.
Note: If the system is configured for the current load command
mode, then the direct load entry will command the desired current,
in Amps, not power, in KW. The load command mode is configured via
the User Configuration settings (ref. 4.2.2 User Config).
Enter required load
[
500] Amps
If a load command is entered that is in excess of the configured maximum
then a warning message will be displayed:
If the Enter key is pressed, the commanded load is accepted. If Escape
(ESC) is pressed then the command is aborted. The maximum load
command is calculated from the configured maximum Preset Load ("E")
value (ref. 4.2.2 User Config).
Inductive Load Bank: On an inductive load bank, the direct load
entry is entered in KVAR units:
Enter required load [
500] KVAR
5.2.1.1 KVAR Calculator
When operating an inductive load bank from either the Local Control
Panel or a connected Remote Control Panel, the system can automatically
calculate the KVARs (kilovolt-amp-reactive) required to produce a given
power factor at a desired load. Simply enter the desired load and power
factor, "500.8" in our example, and press the Enter key. The system will
calculate the required KVARs to achieve 500 KW @ 0.8 power factor,
375 KVAR in our case. If you wish
to apply this load, simply press the
Enter key. Pressing the Escape key will abort the load command.
5.2.1.2 Direct Power Factor Entry
On systems that contain inductive load bank(s), the desired power factor
can be entered directly much like the direct load command. In fact the
desired power factor can be included in the direct load command.
Returning to our previous example, lets include a 0.85 power factor in the
command. From our load command Data Entry Field, we enter "500.85".
Remember that the load command Data Entry Field is activated by