Download ACU+ Controller User Manual
Transcript
NetSure™ ACU+ Controller (Advanced Control Unit Plus) User Instructions, UM1M820BNA (Issue L, December 11, 2014) / ... / SMTemp1 T8 / ... / SMTemp1 T1 / EIB T2 / EIB T1 / IB2 T2 / IB2 T1). You can also select Maximum or Average which takes the maximum or average reading of the temperature probes (any of SMTemp8 T8 / ... / SMTemp8 T1 / ... / SMTemp1 T8 / ... / SMTemp1 T1 / EIB T2 / EIB T1 / IB2 T2 / IB2 T1) set as ambient temperature probes. is set to. It is suggested to leave this value at the default (0.5 volts). • Proportion Coeff: The proportional coefficient that the power system designated as “System A” in a "Power Split" configuration is set to. It is suggested to leave this value at the default (30%). • Amb Temp High2: Allows you to set a high ambient temperature alarm 2 point. • • Amb Temp High1: Allows you to set a high ambient temperature alarm 1 point. Integral Time: The integral time that the power system designated as “System A” in a "Power Split" configuration is set to. It is suggested to leave this value at the default (60 seconds). • Amb Temp Low: Allows you to set a low ambient temperature alarm point. Rectifier • System Temp1: Not used. All Rect Set Menu • System Temp2: Not used. • System Temp3: Not used. • IB2 Temp1: Sets temperature port 1 on the IB2 board to None, Battery, or Ambient. Menu Navigation: Main Menu / Settings / Rectifier / All Rect Set Note: For WEB Interface; menu items are found under Device Information / Rectifier Group / Settings Tab. • IB2 Temp2: Sets temperature port 2 on the IB2 board to None, Battery, or Ambient. • EIB Temp1: Sets temperature port 1 on the EIB board to None, Battery, or Ambient. • EIB Temp2: Sets temperature port 2 on the EIB board to None, Battery, or Ambient. "All Rect Set" Parameter Settings: • HVSD: Enables or disables the High Voltage Shutdown feature for all rectifiers. • Note: You can set High2, High1, and Low temperature alarms for each temperature sensor (from the Web Interface). Note that you cannot set high and low temperature alarms for individual temperature sensors from the Local Menus. High and low temperature alarm settings for the temperature sensors set as ambient are found in the Device Information / Power System / Settings tab. High and low temperature alarm settings for the probes set as battery are found in the Device Information / Battery Group / Settings tab. • Restart on HVSD: Enables or disables the High Voltage Shutdown Restart feature for all rectifiers. • HVSD Restart T: When the High Voltage Shutdown Restart feature is enabled and the output exceeds the high voltage limit, the rectifiers restart after this time period expires. • Start Interval: Sets the sequence start interval (time period between starting each rectifier in the system). • Walk-In: Enables or disables the start-up walk-in feature for all rectifiers. • Walk-In Time: Sets the walk-in time period for all rectifiers. • Turn On ACOverV: Enables or disables the "Turn On AC Over Voltage" feature. When the system is operating on “week” grid input power (i.e. diesel generator), the input voltage may have a very high peak voltage which may cause a rectifier not to turn on. If “Turn On AC Over Voltage" feature is enabled, the rectifier is forced to turn on. • ECO Mode: Enables or disables the Energy Optimization feature for all rectifiers. When enabled, the following parameters can be set. Power Split Menu See also “Power Split Feature” on page 6. Menu Navigation: Main Menu / Settings / Power System / Power Split Note: For WEB Interface; menu items are found under Device Information / Power System / Settings Tab. "Power Split" Parameter Settings: • Power Split Current Limit: Current limit point for power system designated as “System A” in a "Power Split" configuration. • Delta Volt: The offset voltage that the power system designated as “System A” in a "Power Split" configuration Spec. No: 1M820BNA, 1M820DNA Model No: M820B, M820D 91 HVSD Limit: Sets the High Voltage Shutdown point for all rectifiers. • Best Oper Point: Percent of full load capacity that the rectifiers operate under in the Energy Optimization mode. Code: UM1M820BNA Issue L, December 11, 2014