6. BASIC INSTRUCTIONS Applicable CPU Bit device Word (16-bit) device X Y M L S B F T C D W R A0 (S1) O O O O O O O O O O O O O (S2) O O O O O O O O O O O O O A1 Constant Pointer Level Z V K H O O O O O O P I N K1 to K8 O M9012 (M9010, M9011) O Instruction symbol LD (S1) (S2) (S1) AND Error flag Available Device Carry flag All CPUs Index 32-bit data comparison (D=, D<>, D>, D<=, D<,D>=) Digit specification 6.1.2 MELSEC-A . D=, D<>,D> D<=, D<, D>= Setting data (S2) (S1) (S2) Compared data or head number of device which stores compared data OR (S1) Functions (S2) (1) Handled as a NO contact and used for the comparison of 32bits. (2) The comparison operation result is as shown below: Execution Conditions Comparison Operation Result Instruction Symbol in Condition (S1) = (S2) D= (S1) ≠ (S2) D<> (S1) ≠ (S2) D<> (S1) = (S2) D> (S1) > (S2) D> (S1) ≤ (S2) D<= (S1) ≤ (S2) D<= (S1) > (S2) D< (S1) < (S2) D< (S1) ≥ (S2) D>= (S1) ≥ (S2) D>= (S1) < (S2) Instruction Symbol in Condition D= Continuity status The execution conditions of LD , AND , and OR Instruction Comparison Operation Result Non-Continuity status are as indicated below. Execution Condition LD Executed per scan. AND Executed only when the preceding contact instruction is on. OR Executed per scan. 6−6