Download ISO5167 Flow Calculation Program

Transcript
ISO5167 Flow Calculation Program User Manual
Point Type 22: FB103 ISO5167 Setup and Values Parameters
Parm
#
Name
Access
Data Type
Length
Range
Default
16
Expansion Factor
R/O
FLOAT
4
N/A
0.0
Calculated expansion factor of discharge.
17
Reynolds Number
R/O
FLOAT
4
N/A
0.0
Calculated Reynolds Number.
18
Pressure Loss
R/O
FLOAT
4
N/A
0.0
Calculated Pressure Loss.
19
Softpoint Enable
R/W
UINT8
1
0 - 16
0
Description of functionality and meaning
of values
Enables saving calculated data to softpoints.
0=disabled.
1-16 indicates the softpoint logical to use.
20
Calculation Method
R/W
UINT8
1
0-2
2
Select which edition of ISO5167 to be used.
0=91.
1=98.
2=2003
21
Limit Checks
R/W
UINT8
1
0-1
0
Perform limit checks option.
0=disabled.
1=enabled.
22
Reference Temperature
R/W
UINT8
1
0-2
0
Selects reference temperature.
0=15 Deg. C.
1=0 Deg. C.
2=20 Deg. C.
23
Unused
24
Temperature Tap
R/W
UINT8
1
0-1
0
Selects the location of the temperature tap
for the meter run.
0=downstream.
1=upstream.
18
Rev. Nov-09