Download Programming manual (CC
Transcript
Note1: From the most significant digit to 2 figures can be freely set up in the range of 5A to 30000A. Note2: The set-up range is different by setting of phase wiring. ● At 3P4W Corresponds to only 190V, 415V, 440V, setting vaule is changed as follows. Setting value Using VT/ Direct input Direct Voltage 190V 415V 440V Direct input Using VT Using VT 110V/190V ― ― VT secondary Voltage ― 63.5V/110V 63.5V/110V VT primary Voltage ― 240V/415V 254V/440V ● At 3P3W_2CT,3P3W_3CT ◆ When set in the range from 221V to 750000V It is set “Using VT”, and sets the primary voltage which is transmitted. From the most significant digit to 3 figures can be freely set up in the range of 221V to 750000V. ◆ At 110V or 220V It is set “Direct input”, and sets the primary voltage which is transmitted as the direct input voltage. Note3: The set-up range is different by setting of phase wiring. ● At 3P4W ◆ When set in the range from 278V to 750000V It is set “Using VT”, and sets the primary voltage which is transmitted. From the most significant digit to 3 figures can be freely set up in the range of 278V to 750000V. ◆ At the 63.5V, 100V, 110V, 220V, 240V, 254V or 277V It is set “Direct input”, and sets the primary voltage which is transmitted as the direct input voltage. ● At 3P3W_2CT,3P3W_3CT The error code of invalid channel number is replied. Note4: The range of time constant is as follows. It is set by seconds. 0s, 10s, 20s, 30s, 40s, 50s, 1min, 2min, 3min, 4min, 5min, 6min, 7min, 8min, 9min, 10min, 15min, 20min, 25min, 30min. Note5: The multiplicand value is changed by the set-up value of phase wiring, primary voltage, and primary current. (Refer to P. 30) (33/n) LEN080334