Download 8 - DEMPAN
Transcript
6 76(209) 6.6.4.7 Multi-purpose Control Application Digital inputs (Control keypad: Menu M2 G2.2.4) Code P2.2.7.1 P2.2.7.2 P2.2.7.3 Parameter Start signal 1 Start signal 2 Run enable Min 0 0 0 Default A.1 A.2 0.2 P2.2.7.4 Reverse 0 0.1 412 P2.2.7.5 P2.2.7.6 P2.2.7.7 0 0 0 0.1 0.1 0.1 419 420 421 0 0.1 417 0 0.1 418 P2.2.7.10 P2.2.7.11 P2.2.7.12 Preset speed 1 Preset speed 2 Preset speed 3 Motor potentiometer reference DOWN Motor potentiometer reference UP Fault reset External fault (close) External fault (open) 0 0 0 0.1 0.1 0.2 414 405 406 P2.2.7.13 Acc/Dec time selection 0 0.1 408 P2.2.7.14 P2.2.7.15 Acc/Dec prohibit DC braking 0 0 0.1 0.1 415 416 P2.2.7.16 Jogging speed 0 A.4 413 P2.2.7.17 AI1/AI2 selection 0 0.1 422 P2.2.7.18 Control from I/O terminal 0 0.1 409 P2.2.7.19 Control from keypad 0 0.1 410 P2.2.7.20 Control from fieldbus 0 0.1 411 P2.2.7.21 Parameter set 1/set 2 selection 0 0.1 496 P2.2.7.22 Motor control mode 1/2 0 0.1 164 0 0.2 750 0 0.2 1210 0 0 0.2 0.1 1420 532 P2.2.7.8 P2.2.7.9 NXP drives only P2.2.7.23 Cooling monitor External brake P2.2.7.24 acknowledge P2.2.7.25 Prevention of startup P2.2.7.26 Enable inching Cust ID 403 404 407 P2.2.7.27 Inching reference 1 0 0.1 530 P2.2.7.28 Inching reference 2 0 0.1 531 P2.2.7.29 Reset encoder counter 0 0.1 1090 P2.2.7.30 P2.2.7.31 Emergency stop Master Follower mode 2 Input switch acknowledgement 0 0 0.2 0.1 1213 1092 0 0.2 1209 P2.2.7.32 Note Motor start enabled (cc) Direction forward (oc) Direction reverse (cc) See preset speeds in Basic Parameters (G2.1) Mot.pot. reference decreases (cc) Mot.pot. reference increases (cc) All faults reset (cc) Ext. fault displayed (cc) Ext. fault displayed (oc) Acc/Dec time 1 (oc) Acc/Dec time 2 (cc) Acc/Dec prohibited (cc) DC braking active (cc) Jogging speed selected for frequency reference (cc) Force control place to I/O terminal (cc) Force control place to keypad (cc) Force control place to fieldbus (cc) Closed cont.=Set 2 is used Open cont.=Set 1 is used Closed cont.=Mode 2 is used Open cont.=Mode 1 is used See par 2.6.1, 2.6.12 Used with liquid-cooled unit Monitoring signal from mechanical brake Safety switch input Enables Inching function Inching reference 1. This will start the drive Inching reference 2. This will start the drive Reset monitoring signals, shaft rounds and angle Table 6-12. Digital input signals, G2.2.4 cc = closing contact oc = opening contact