Download 8 - DEMPAN
Transcript
Description of parameters 600 Motor control mode 234567 171(209) (2.6.1) NXS: 0 Frequency control: The I/O terminal and keypad references are frequency references and the frequency converter controls the output frequency (output frequency resolution = 0.01 Hz) 1 Speed control: The I/O terminal and keypad references are speed references and the frequency converter controls the motor speed compensating the motor slip (accuracy ± 0,5%). 2 Torque control (Multi-Purpose Control application only) In torque control mode, the references are used to control the motor torque. The following selections are available for NXP drives in applications 2, 3, 4, 5 and 7. Selections 5 and 6 are not available in application 6 (Multipurpose Control Application). 601 3 Speed crtl (closed loop) The I/O terminal and keypad references are speed references and the frequency converter controls the motor speed very accurately comparing the actual speed received from the tachometer to the speed reference (accuracy ±0.01%). 4 Torque crtl (closed loop) The I/O terminal and keypad references are torque references and the frequency converter controls the motor torque. Switching frequency 234567 (2.6.9) Motor noise can be minimised using a high switching frequency. Increasing the switching frequency reduces the capacity of the frequency converter unit. The range of this parameter depends on the size of the frequency converter: Type 0003—0061 NX_5 0003—0061 NX_2 0072—0520 NX_5 0041—0062 NX_6 0144—0208 NX_6 Min. [kHz] Max. [kHz] Default [kHz] 1.0 16,0 10.0 1.0 10.0 3.6 1.0 6.0 1.5 Table 8-12. Size-dependent switching frequencies Note! The actual switching frequency might be reduced down to 1,5kHz by thermal management functions. This has to be considered when using sine wave filters or other output filters with a low resonance frequency. 602 Field weakening point 234567 (2.6.4) The field weakening point is the output frequency at which the output voltage reaches the set (ID603) maximum value. 8