Download 8 - DEMPAN

Transcript
6
76(209)
6.6.4.7
Multi-purpose Control Application
Digital inputs (Control keypad: Menu M2
G2.2.4)
Code
P2.2.7.1
P2.2.7.2
P2.2.7.3
Parameter
Start signal 1
Start signal 2
Run enable
Min
0
0
0
Default
A.1
A.2
0.2
P2.2.7.4
Reverse
0
0.1
412
P2.2.7.5
P2.2.7.6
P2.2.7.7
0
0
0
0.1
0.1
0.1
419
420
421
0
0.1
417
0
0.1
418
P2.2.7.10
P2.2.7.11
P2.2.7.12
Preset speed 1
Preset speed 2
Preset speed 3
Motor potentiometer
reference DOWN
Motor potentiometer
reference UP
Fault reset
External fault (close)
External fault (open)
0
0
0
0.1
0.1
0.2
414
405
406
P2.2.7.13
Acc/Dec time selection
0
0.1
408
P2.2.7.14
P2.2.7.15
Acc/Dec prohibit
DC braking
0
0
0.1
0.1
415
416
P2.2.7.16
Jogging speed
0
A.4
413
P2.2.7.17
AI1/AI2 selection
0
0.1
422
P2.2.7.18
Control from I/O terminal
0
0.1
409
P2.2.7.19
Control from keypad
0
0.1
410
P2.2.7.20
Control from fieldbus
0
0.1
411
P2.2.7.21
Parameter set 1/set 2
selection
0
0.1
496
P2.2.7.22
Motor control mode 1/2
0
0.1
164
0
0.2
750
0
0.2
1210
0
0
0.2
0.1
1420
532
P2.2.7.8
P2.2.7.9
NXP drives only
P2.2.7.23
Cooling monitor
External brake
P2.2.7.24
acknowledge
P2.2.7.25
Prevention of startup
P2.2.7.26
Enable inching
Cust
ID
403
404
407
P2.2.7.27
Inching reference 1
0
0.1
530
P2.2.7.28
Inching reference 2
0
0.1
531
P2.2.7.29
Reset encoder counter
0
0.1
1090
P2.2.7.30
P2.2.7.31
Emergency stop
Master Follower mode 2
Input switch
acknowledgement
0
0
0.2
0.1
1213
1092
0
0.2
1209
P2.2.7.32
Note
Motor start enabled (cc)
Direction forward (oc)
Direction reverse (cc)
See preset speeds in Basic
Parameters (G2.1)
Mot.pot. reference decreases
(cc)
Mot.pot. reference increases
(cc)
All faults reset (cc)
Ext. fault displayed (cc)
Ext. fault displayed (oc)
Acc/Dec time 1 (oc)
Acc/Dec time 2 (cc)
Acc/Dec prohibited (cc)
DC braking active (cc)
Jogging speed selected for
frequency reference (cc)
Force control place to I/O
terminal (cc)
Force control place to
keypad (cc)
Force control place to
fieldbus (cc)
Closed cont.=Set 2 is used
Open cont.=Set 1 is used
Closed cont.=Mode 2 is used
Open cont.=Mode 1 is used
See par 2.6.1, 2.6.12
Used with liquid-cooled unit
Monitoring signal from
mechanical brake
Safety switch input
Enables Inching function
Inching reference 1. This will
start the drive
Inching reference 2. This will
start the drive
Reset monitoring signals,
shaft rounds and angle
Table 6-12. Digital input signals, G2.2.4
cc = closing contact
oc = opening contact