Download Programming manual ATV66
Transcript
Total unlock : drive initialization Drive initialization Select Drive initialization mode in the Main menu. ENT ESC 9‘DRIVE INIT. TOTAL FACTORY SETT. PARTIAL FACT. SETT. USER SETTING STORE RECALL USER SETTING When this mode is used, the motor must be stationary. This mode is used to return to factory settings : – either totally, – or partially. It can also be used to download the configuration and all the settings remotely onto a blank PCMCIA card which can be installed on the speed controller. Conversely, after a PCMCIA card to which data has been remotely downloaded has been installed, this mode is used to transfer data to the speed controller. Return to factory settings Total return 9.1‘TOT.FACTORY SETT Do you want to change all the parameters to factory settings? ENT to confirm ESC to abort THIS ACTION CLEAR THE ACTUAL CONFIGURATION AND SETTINGS ENT Are you sure ? ENT to confirm Warning message Partial return 9.2‘PARTIAL FACTORY DISPLAY CONFIG. KEYPAD CONFIG. GENERAL CONFIG. Select the block to be initialized ‘ ENT THIS ACTION CLEAR THE ACTUAL CONFIGURATION AND SETTINGS OF : Are you sure ? ENT to confirm ENT Select the required mode to be reset to factory settings. Warning message with indication of the mode selected Comment : a total return to factory settings returns the speed controller to its initial state before the first power-up (see pages 4 and 8). 67