Download - ISI D. Gatermann

Transcript
Configuring
4.11 Planning subnets
Differences in the MPI addresses of CPs/FMs in an S7300 system
Table 4- 13
MPI addresses of CPs/FMs in an S7-300 system
Options
Example
Example:
A system containing an S7-300 CPU and 2 CPs.
&38
&3
&3
60
You have two options of assigning MPI
addresses to CPs/FMs installed in a system:
CPU
CP
MPI addr.
MPI addr. + x MPI addr. + y
2nd option: The CPU automatically assigns MPI MPI addr.
addresses to the CPs in its system, based on the
following syntax: MPI address CPU; MPI
address + 1; MPI addr. + 2.
MPI addr. + 1 MPI addr. + 2
1st option: The CPU accepts the MPI addresses
you set for the CPs in STEP 7.
CP
SM
(Default)
Special feature:
CPU 314C-2 PN/DP, CPU 315-2 PN/DP, CPU
317 and CPU 319-3 PN/DP
When the central rack of an S7-300 contains
FM/CPs with their own MPI address, the CPU
forms its own communication bus via the
backplane bus for these FM/CPs and separates it
from the other subnets.
The MPI address of those FM/CPs is thus no
longer relevant for the nodes on other subnets.
The MPI address of the CPU is used to
communicate with these FMs/CPs.
Recommendation for MPI addresses
Reserve MPI address "0" for a service PG, or "1" for a service OP, for temporary
connections of these devices to the subnet. You should therefore assign different MPI
addresses to PGs/OPs operating on the MPI subnet.
Recommended MPI address of the CPU for replacement or service operations:
Reserve MPI address "2" for the CPU. This prevents duplication of MPI addresses after you
connect a CPU with default settings to the MPI subnet (for example, when replacing a CPU).
You should assign an MPI address greater than "2" to CPUs in the MPI subnet.
Recommendation for PROFIBUS addresses
Reserve PROFIBUS address "0" for a service PG that you can subsequently connect briefly
to the PROFIBUS subnet as required. You should therefore assign unique PROFIBUS
addresses to PGs integrated in the PROFIBUS subnet.
PROFIBUS DP: Electrical cables or fiber-optic cables?
Use fiber optic cables on a field bus with greater length, rather than copper conductors, in
order to be independent on the transmission rate, and to exclude external interference.
CPU 31xC and CPU 31x: Installation
60
Operating Instructions, 03/2011, A5E00105492-12