Download - ISI D. Gatermann
Transcript
Appendix A.2 Protection against electromagnetic interference Cables for ... and cables for ... Run ... DC voltage (> 60 V and ≤ 400 V), unshielded Bus signals, shielded (for example, PROFIBUS, PROFINET) AC voltage (> 25 V and ≤ 400 V), unshielded Data signals, shielded (programming devices, operator panels, printers, counter inputs, etc.) Analog signals, shielded DC voltage ( ≤ 60 V), unshielded Process signals ( ≤ 25 V), shielded AC voltage (≤ 25 V), unshielded Monitors (coaxial cable) DC voltage (> 60 V and ≤ 400 V), unshielded AC voltage (> 25 V and ≤ 400 V), unshielded DC and AC voltage (> 400 V), unshielded In separate bundles or cable ducts (no minimum clearance necessary) In common bundles or cable ducts Inside cabinets: In separate bundles or cable ducts (no minimum clearance necessary) Outside cabinets: On separate cable racks with a clearance of at least 10 cm DC and AC voltage (> 400 V), unshielded Inside cabinets: Bus signals, shielded (e.g. PROFIBUS, PROFINET) In separate bundles or cable ducts (no minimum clearance necessary) Data signals, shielded (programming devices, operator panels, printers, counter inputs, etc.) Outside cabinets: On separate cable racks with a clearance of at least 10 cm Analog signals, shielded DC voltage ( ≤ 60 V), unshielded Process signals ( ≤ 25 V), shielded AC voltage (≤ 25 V), unshielded Monitors (coaxial cable) DC and AC voltage (> 400 V), unshielded In common bundles or cable ducts CPU 31xC and CPU 31x: Installation 276 Operating Instructions, 03/2011, A5E00105492-12