To Installers
Boiler Installation
Draught Regulator
ATTENTION
The chimney draught should be at least 18 Pa
(20 kW) and 22 Pa (30 kW). If such parameters
cannot be ensured, disassemble a couple of turbulators or use an exhaust fan.
Swing axle adjustment
After the installation, slightly loosen two lock screws and
turn the swing axle so, that it would be in horizontal position after closing the draught regulator. Retighten the lock
screws.
The chimney draught depends upon its diameter, height,
building location, wind conditions, external temperature,
boiler power output, flue gas temperature and soot accumulation in the chimney.
Most boilers operated currently are connected to older
types of chimneys. Sometimes, their diameters and insulation are not adequate for the new types of fuel.
Large fluctuations in draught can cause some disturbances
in the boiler combustion chamber operating conditions. In
order to minimize these deviations and the risk of damage
caused by condensation in the chimney, we recommend
the installation of a draught regulator in the boiler flue.
Lock screws
LEK
Draught regulator installation
Design of the draught regulator allows its installation in the
flues in any orientation: vertical, horizontal or inclined. The
controllers are installed on an adapter plate that replaces
the existing cleanout.
Draught control
Adjust draught with the throttle opened by holding the clip
with a weight and shifting it along the guide. Each shifting
of the weight of 2 mm corresponds to 1 Pa. These are
approximate values and you should measure them with a
micro pressure gauge.
X
By default, the controller is set to 10 Pa.
LEK
Correct adjustment should ensure smooth and even opening of the throttle when the boiler is switched OFF.
LEK
PELLUX 100/20, PELLUX 100/30