Local Operation Auxiliary Auto Start Mode The Auxiliary Auto Start mode determines the state of the auxiliary output after a complete power cycle (all front panel LEDS are not illuminated). With Auxiliary Auto Start mode turned to On, the auxiliary output will be activated after the power supply is powered up again. To define the Auxiliary Auto Start mode: 1. Press and hold the OUTPUT ENABLE Aux button for 1 second. or is displayed. 2. To change to status to On or Off, press the OUTPUT ENABLE Aux button. 3 The SCPI command (s) for these instructions are: [:]OUTPut[<channel>]:AUXiliary:PowerON[:STATe] Constant Power Mode (version 2.21 and higher) In Constant Power Mode the power supply will continually adjust the current levels to maintain a constant power set point. This mode is intended primarily for loads with response time greater than approximately 100ms. In order to provide additional protection for the load, voltage and current limits may be set while in the constant power mode. If the unit cannot regulate to the Constant Power setting due to load conditions, it will regulate at either the voltage or the current limit depending on the load demand. Example, CP Mode: Constant Power set 500W Voltage limit 61V Current limit 20A To activate Constant Power mode and set the value: M370430-01 Rev C 3. Turn the 9-position mode control to the FLD position or press the rotary Adjust/Enter control if the 9-position mode control is already at the FLD position. 4. Turn the rotary Adjust/Enter control until “ΦΛΔ ΧΠ” is displayed. 5. Press the rotary Adjust/Enter control. 6. Turn the Adjust/Enter control to the desired set point. 7. Press the rotary Adjust/Enter control 8. Turn the Adjust/Enter control control for fine adjustment. 3-19