Download book 2PDF file
Transcript
Comfort Control Manual (Installation and Applications) Example: Duration of quick setback if Comfort Setpoint minus Reduced Setpoint = 2 °C (Comfort Setpoint = 20 °C, Reduced Setpoint =18 °C) . Quick setback operation table Composite external temperature: Building time constant: Quick setback duration (hours) Figure 67 Example of heating operation depending on the temperature setpoints 15. Parameter “6110: Time constant building” (default 20 h, range: 0 to 50 h), when the external temperature varies, the room temperature changes in relation to the thermal storage capacity of the building. This function is used to correct the response of the delivery setpoint to changes in the external temperature. Example: • > 20: the room temperature responds more slowly to changes in the external temperature. • 10 ÷ 20: This setting can be used for the majority of buildings. • < 10 the room temperature responds more quickly to changes in the external temperature. 16. Parameters “790, 1090 and 1390: Optimum start control max”; passage from one temperature level to another (reduced to comfort) is optimised so that the Comfort setpoint can be reached in the respective “Activation switching time” (Xein). The switching time in question can be set with parameters: • 790 for circuit C1. • 1090 for circuit C2. • 1390 for circuit CP. “Optimum start control” is possible with or without room units. 92 Ed. 12/2008