Comfort Control Manual (Installation and Applications)
o Manual setpoint: The delivery temperature setpoint for the manual floor
curing function can be entered independently for each heating circuit.
o Current setpoint: Indicates the current delivery temperature setpoint for the
current floor curing function.
o Current day: Indicates the current day for the current floor curing function.
o Completed days: If the floor curing function is aborted, the number of whole
days for which it ran is stored; this is stored in memory until the function is
initiated again.
Floor curing function with “temperature profile”:
• The temperature profile selected in parameter “Floor curing function” (“850”,
“1150” and “1450”) is run automatically by the controller.
Floor curing function with “temperature profile” diagram
Figure 70
•
•
•
•
96
Example of operation of the “floor curing function”. X: start day; Fh: functional heating; Bh: curing
heating.
The temperature profile is kept between “TVMmin: Flow temp setpoint min”
(parameters: “740”, “1040” and “1340”) and “TVmax: Flow temp setpoint max”
(parameters: “741”, “1041” and “1341”). The temperature change always
occurs at midnight.
The floor curing temperature profile is the same for all heating circuits (C1, C2
and CP).
The setpoint (TVw) used on the start day is the setpoint of the first day of
operation.
The floor curing function terminates when the number of days of operation set
by the controller has expired or if it is deactivated by the respective parameter:
“Floor curing function” = “Off”. The start day (day0), the day from the time of
activation to midnight, is not counted as a day of operation.
Ed. 12/2008