Download Reference Manual 70 & 700 Adjustable Frequency AC Drive
Transcript
MOP 2-115 Direction Mask 0 0 0 0 0 1 0 0 Adapter # X 6 5 4 3 2 1 0 This “masks out” the reverse function from all adapters except Adapter 2, making the local HIM (Adapter 1) REV button inoperable. Also see Owners on page 2-127. MOP The Motor Operated Pot (MOP) function is one of the sources for the frequency reference. The MOP function uses digital inputs to increment or decrement the Speed reference at a programmed rate. The MOP has three components: • [MOP Rate] parameter • [Save MOP Ref] parameter • [MOP Frequency] parameter MOP increment input MOP decrement input The MOP reference rate is defined in [MOP rate]. The MOP function is defined graphically below MOP dec MOP inc MOP reference MOP rate is defined in Hz/sec. The MOP reference will increase/decrease linearly at that rate as long as the MOP inc or dec is asserted via TB or DPI port (the MOP inputs are treated as level sensitive). Both the MOP inc and dec will use the same rate (i.e. they can not be separately configured). The MOP rate is the rate of change of the MOP reference. The selected active MOP reference still feeds the ramp function to arrive at the present commanded speed/frequency (eg. is still based on the accel/decel rates). Asserting both MOP inc and dec inputs simultaneously will result in no change to the MOP reference. [Save MOP Ref] is a packed boolean parameter with two bits used as follows: Bit 0 0 = Don’t save MOP reference on power-down (default) 1 = Save MOP reference on power-down