2-162
Skip Frequency
Skip Frequency Examples
The skip frequency will have
hysteresis so the output does not
toggle between high and low
values. Three distinct bands can
be programmed. If none of the
skip bands touch or overlap, each
band has its own high/low limit.
Max. Frequency
Skip Frequency 1
Skip Band 1
Skip Frequency 2
Skip Band 2
0 Hz
If skip bands overlap or touch, the
center frequency is recalculated
based on the highest and lowest
band values.
400 Hz.
Skip Frequency 1
Skip Frequency 2
Adjusted
Skip Band
w/Recalculated
Skip Frequency
0 Hz
If a skip band(s) extend beyond
the max frequency limits, the
highest band value will be
clamped at the max frequency
limit. The center frequency is
recalculated based on the highest
and lowest band values.
400 Hz.
Max.Frequency
Skip
Adjusted
Skip Band
w/Recalculated
Skip Frequency
0 Hz
If the band is outside the limits,
the skip band is inactive.
400 Hz.
Skip Frequency 1
Inactive
Skip Band
60 Hz. Max.
Frequency
0 Hz
Acceleration and deceleration are not affected by the skip frequencies.
Normal accel/decel will proceed through the band once the commanded
frequency is greater than the skip frequency. See (A) & (B) in Figure 2.30.
This function affects only continuous operation within the band.