Download Manual - OMEGA Engineering
Transcript
Time Pv Alarm Spv 4 Hysteresis parameter < 0 On Off On Off Alarm output Absolute alarm with controller in cooling functioning (par. 11 Act.t. selected CooL) and hysteresis value less than “0” (par. 28 A.1.HY. < 0). N.B.* Absolute Alarm or Threshold Alarm Referring to Setpoint Command ( a.c.AL. selection) Comand Spv Hysteresis parameter > 0 Alarm Spv 1 Time On Off 54 - CN245 - User manual Off Alarm output Absolute alarm refers to the command set, with the controller in heating functioning (par. 11 Act.t. selected Heat) and hysteresis value greater than “0” (par. 28 A.1.HY. > 0). The command set can be changed by pressing the arrow keys on front panel or using serial port RS485 commands. N.B.*