Modbus Interface
When the inner current loop is enabled, the output of the voltage loop’s PI controller is the
commanded current to the inner current loop. In this case, the PI output is scaled such that an
output of zero indicates no current and an output of 1.0 indicates the full scale current
specified in the Current Feedback Analog Full Scale configuration register (0x105C). When
operating in this scenario, the Voltage Control Min/Max Output clamp values are used to
clamp the current command using this same scaling. This effectively acts as the active current
limit for voltage control mode.
5.4.7.8 Inner Current Loop Enable
This parameter enables the inner current loop when operating in voltage control mode. As
described in the previous section, with the current loop disabled the output of the voltage loop
is used to modify the SCR trigger angle in order to regulate the output DC link voltage. With the
inner current loop enabled, the output of the voltage loop commands a DC current output in
order to regulate the DC link voltage. The current loop, in turn, modifies the SCR trigger angle
in order to regulate the output current.
INNER CURRENT
LOOP ENABLE
VOLTAGE
SETPOINT
PI
CONTROL
VOLTAGE
FEEDBACK
MUX
FIRING
ANGLES
Current
Controller
5.4.8 DC Current Control Parameters
Table 27 - Configuration Register Set – DC Current Control Parameters
Address
Decimal
Hex
4184
4185
4186
4187
4188
4189
4190
4191
4192
4193
4196
4197
4198
4199
0x1058
0x1059
0x105A
0x105B
0x105C
0x105D
0x105E (LSW)
0x105F (MSW)
0x1060 (LSW)
0x1061 (MSW)
0x1064 (LSW)
0x1065 (MSW)
0x1066 (LSW)
0x1067 (MSW)
Register Name
Data
Type
Units
Factory
Default
Min
Max
Access
Level
Current Control Mode
Default Current Setpoint
I Setpoint Analog Input Select
I Feedback Analog Input Select
Current Feedback Full Scale
Current Setpoint Slew Limit
U16
U16
U16
U16
U16
U16
ENUM
0.1%
ENUM
ENUM
1A
1 A/sec
0
0
0
3
1000
100
0
0
0
0
0
1
1
1000
2
3
65535
65535
R/W
R/W
R/W
R/W
R/W
R/W
Current Control Proportional Gain Kp
S32
Q16
1.0
0.0
10000.0
R/W
Current Control Integral Gain Ki
S32
Q16
0.0
0.0
10000.0
R/W
Current Control Max Output, Iomax
S32
Q16
1.0
0.0
10000.0
R/W
Current Control Min Output, Iomin
S32
Q16
0.0
0.0
10000.0
R/W
5.4.8.1 Current Control Mode
When operating in closed loop current control mode, this register selects the source of the
current setpoint; either an analog input or a Modbus register. When the current controller is
being operated as an inner current loop in a mode other than direct current control, the
setpoint input is used to specify the current limit value.
Publication UM-0040