Download AFE Controller User`s Manual
Transcript
Modbus Interface When the inner current loop is enabled, the output of the voltage loop’s PI controller is the commanded current to the inner current loop. In this case, the PI output is scaled such that an output of zero indicates no current and an output of 1.0 indicates the full scale current specified in the Current Feedback Analog Full Scale configuration register (0x105C). When operating in this scenario, the Voltage Control Min/Max Output clamp values are used to clamp the current command using this same scaling. This effectively acts as the active current limit for voltage control mode. 5.4.7.8 Inner Current Loop Enable This parameter enables the inner current loop when operating in voltage control mode. As described in the previous section, with the current loop disabled the output of the voltage loop is used to modify the SCR trigger angle in order to regulate the output DC link voltage. With the inner current loop enabled, the output of the voltage loop commands a DC current output in order to regulate the DC link voltage. The current loop, in turn, modifies the SCR trigger angle in order to regulate the output current. INNER CURRENT LOOP ENABLE VOLTAGE SETPOINT PI CONTROL VOLTAGE FEEDBACK MUX FIRING ANGLES Current Controller 5.4.8 DC Current Control Parameters Table 27 - Configuration Register Set – DC Current Control Parameters Address Decimal Hex 4184 4185 4186 4187 4188 4189 4190 4191 4192 4193 4196 4197 4198 4199 0x1058 0x1059 0x105A 0x105B 0x105C 0x105D 0x105E (LSW) 0x105F (MSW) 0x1060 (LSW) 0x1061 (MSW) 0x1064 (LSW) 0x1065 (MSW) 0x1066 (LSW) 0x1067 (MSW) Register Name Data Type Units Factory Default Min Max Access Level Current Control Mode Default Current Setpoint I Setpoint Analog Input Select I Feedback Analog Input Select Current Feedback Full Scale Current Setpoint Slew Limit U16 U16 U16 U16 U16 U16 ENUM 0.1% ENUM ENUM 1A 1 A/sec 0 0 0 3 1000 100 0 0 0 0 0 1 1 1000 2 3 65535 65535 R/W R/W R/W R/W R/W R/W Current Control Proportional Gain Kp S32 Q16 1.0 0.0 10000.0 R/W Current Control Integral Gain Ki S32 Q16 0.0 0.0 10000.0 R/W Current Control Max Output, Iomax S32 Q16 1.0 0.0 10000.0 R/W Current Control Min Output, Iomin S32 Q16 0.0 0.0 10000.0 R/W 5.4.8.1 Current Control Mode When operating in closed loop current control mode, this register selects the source of the current setpoint; either an analog input or a Modbus register. When the current controller is being operated as an inner current loop in a mode other than direct current control, the setpoint input is used to specify the current limit value. Publication UM-0040 53