6–10 Using the 160-IB1 on InterBus This is an example of a read drive parameter (all values in hex) The first node on the network is a communication reference (CR) = 2, with the parameter read access index of 5FF0 (see table 5E) and the sub-index specifying parameter 8 [Heatsink Temperature]. Once transmitted, the response in N7:80 provides an echo of the command word N7:81 number of words following N7:82 CR N7:83 result of comms 0=success N7:84 number of bytes read (in this case 1 word) N7:85 data read 45 hex = 69 decimal which is the normal value registered on the heatsink, when temperature is below it. This is an example of a read attribute drive parameter (all values in hex) The first node on the network is a communication reference (CR) = 2, with the parameter read attribute access index of 5FF4 (see table 5E), and the sub-index specifying parameter 30 [Accel Time 1]. Once transmitted, the response is similar to above: N7:85 LSB of 1E is parameter 30, MSB of 1 is multiplier (see table 5F). This is an example of a write attribute drive parameter (all values in hex) In this example the write access index is 5FF9 (see table 5E) and the sub-index specifying parameter 30 [Accel Time 1]. N7:73 specifies the number of bytes to write N7:74 is the data to write N7:80 provides an echo of the command word N7:81 number of words following N7:82 CR N7:83 result of comms 0=success N7:84 & N7:85 are not valid, being values that were updated on the read attribute exercise.