Download User Manual - Schneider
Transcript
Configuration and Programming with Unity Pro Name CLOCK_FAILURE CLOCK_NOT_SYNC Type Bit Description BOOL 1 2 bit 1 = 1 & bit 2 = 1, since If power- on CRA adapter has not received a response from NTP server. bit 1 = 0 & bit 2 = 1, CRA adapter has received a response from NTP server in the past but is not currently receiving the time from the NTP server bit 1 = 0 & bit 2 = 0, Time is valid, CRA adapter is receiving responses from the NTP server. BUFF_FULL BOOL 3 The local drop event buffer is full. TS_BUF_FILLED_PCTAGE BYTE — This byte reports the percentage of the local drop event buffer filled (0...100). TS_EVENTS_STATE BYTE — Refer to Main States (see page 64). PORT1_LINK BOOL 0 0 = Port 1 (ETH1) link is down. PORT2_LINK BOOL 1 0 = Port 2 link is down. PORT3_LINK BOOL 2 0 = Port 3 link is down. ETH_BKP_PORT_LINK BOOL 3 ETH_STATUS (BYTE) 1 = Port 1 (ETH1) link is up. 1 = Port 2 link is up. 1 = Port 3 link is up. 0 = Ethernet backplane link is down. 1 = Ethernet backplane link is up. RPI_CHANGE BOOL 4 RPI change: EtherNet/IP RPI change is in progress (during CCOTF). (reserved bit) — 6 — GLOBAL_STATUS BOOL 7 0 = At least 1 service is not operating normally. NOTE: Refer to the SERVICE_STATUS byte below. 62 1 = All services are operating normally. EIO0000001584 09/2014