VersiStart i III Power Terminations NOTE For personnel safety, the power terminals on models up to VS i III 105 are protected by snap-off tabs. When using large cables, it may be necessary to break off these tabs. NOTE Some units use aluminium busbars. When connecting power terminations, we recommend cleaning the surface contact area thoroughly (using an emery or stainless steel brush) and using an appropriate jointing compound to prevent corrosion. Use only copper stranded or solid conductors, rated for 75 ºC or higher. VS i III 23~VS i III 105 Cable size: 2 11290 .A 6-50 mm (AWG 10-1/0) Torque: 4 Nm (2.9 ft-lb) Torx T20 x 150 Flat 7 mm x 150 14 mm (0.55 inch) VS i III 145 19 Nm (14.0 ft-lb) VS i III 170~VS i III 220 38 Nm (28.0 ft-lb) VS i III 255 38 Nm (28.0 ft-lb) 11 mm (M10) 10.5 mm (M10) 19 mm 19 mm 6 mm VS i III 350~VS i III 425 38 Nm (28.0 ft-lb) 13181.B 08351.B 08352.B 8.5 mm (M8) 6 mm VS i III 500~VS i III 1000 38 Nm (28.0 ft-lb) 11 mm (M10) VS i III 255N 38 Nm (28.0 ft-lb) 10.5 mm (M10) 08353.B 09866.B 14543.A 11 mm (M10) 6 mm 28 mm 5 mm 28 mm 32 mm 13 mm VS i III 360N~VS i III 930N 38 Nm (28.0 ft-lb) 6 mm 32 mm VS i III 1200N~VS i III 1600N 66 Nm (48.7 ft-lb) 12.5 mm (M12) 08354.B 10.5 mm (M10) 32 mm 13 mm 08355.B 05966.E 5.7 14 51 mm 16 mm