Download Operation Manual - Bosch Security Systems
Transcript
164 en | Panels Admin ALLPLEX Access Easy Master Controller Input/Output Description Request-to-Exit (Tog- This input is edge triggered from '0' to '1' (leading edge) & toggling. gle) It activates the Door Strike output for a period of the Door Strike Duration when a leading edge is detected. Door Contact (Level) This input is edge triggered from '0' to '1' (leading edge). It activates the Door Forced Open output when a leading edge is detected and a period of the Door Forced Open Alarm Delay Duration has passed. Lock/Unlock Door Permanently locks/unlocks the door when activated. Door Strike Driven to high for a period of Door Strike Duration when a leading edge is detected at Request-to-Exit. Door Forced Open Driven to high for the duration when Door Contact is high when a leading edge is detected at Door Contact and the Door Forced Open Alarm Delay Duration has lapsed. Door Held Open Driven to high when the Door Strike Duration is over and subsequently, the Door Open Duration is over. The timing diagram below gives a graphical description of the function Ver 1.0.1 | 2012.10 Software Manual Robert Bosch (SEA) Pte Ltd