5.3.2 Fan error This scheme is intended only for the installer. Extract or supply fan stopped Maintenance by the end user is not only dangerous but also has a negative effect on the warranty. Pull the plug out of the socket Open the front lid of the unit Put the plug back in the socket Are both fans turning? Yes No Open the cover of the control board No Ja Measure (within 1 minute after putting the plug back in) if there is a voltage between 0 and 10 volts on the poles 0 and U1 or U2 as shown in section 6.5. Is the voltage correct? Measure (within 1 minute after putting the plug back in) if there is a voltage of 230V on the poles K1 (see scheme section 6.3). Is the voltage correct? No No Pull the plug out of the socket, replace the cables of the fans and put the plug back in the socket Pull the plug out of the socket Pull the plug out of the socket If this does not work or when this is not possible, replace the complete fan set and put the plug back in the socket Replace the control board and put the plug back in the socket Replace the control board and put the plug back in the socket 19