APPENDICES (21)CH1 Process alarm lower lower limit value (Un\G86) to CH8 Process alarm A upper upper limit value (Un\G117) Common Set the digital output value range for each channel. Configure the 4-step setting of process alarm upper upper limit value, process alarm upper lower limit value, process alarm lower upper limit value, and process alarm lower lower limit value. For details on warning output function (process alarm), refer to the following. • Warning Output Function (Process Alarm) ( Page 85, Section 8.9) (a) Setting range • Setting range is -32768 to 32767. • When a value which does not satisfy the formula of process alarm upper upper limit value process alarm upper lower limit value process alarm lower upper limit value process alarm lower lower limit value is set to a channel, an error occurs in the channel. The error code is stored in Latest error code (Un\G19), and Error flag (XF) turns on. The operation is performed in the setting configured before the error occurrence. • When the following functions are used, warning targets are scaling values that reflect the operations of each function. Set values considering operation results of each function. Module Functions L60AD4 Digital clipping function, scaling function, shift function, or difference conversion function L60ADVL8, L60ADIL8 Scaling function (b) Enabling the setting Turn on and off Operating condition setting request (Y9) to enable the setting. (c) Default value Appendix 2 Details of Buffer Memory Addresses 0 is set as the default value. Change the setting value to use the warning output function (process alarm), since 0 is set as the default value. 211