Download EGCP-2 Engine Generator Control Package
Transcript
Manual 26174 EGCP-2 Engine Generator Control Package Standard Sequence: Single No Parallel Unit in Auto with Loss Of Mains Detection Enabled. LOM Action Delay Expires LOM Action Delay Starts Fast Transfer Delay Gen Stable Delay Mains in Spec. Mains Stable Delay Genset On Load Fast Transfer Delay Mains In Spec and On Load Close Mains Breaker Open Gen Breaker Mains in Spec. Gen Breaker Closes To Dead Bus Gen Stable. Start Fast Transfer Delay Open Mains Breaker Start Genset Mains Out of Spec* VIS-110 00-04-27 TIME *Over/Under Frequency and/or Over/Under Voltage Figure 5-5. Loss of Mains Detection Active Standard Sequence: Single Mains Parallel Unit in Auto with Loss Of Mains Detection Enabled. LOM Action Delay Expires LOM Action Delay Starts Gen Stable Delay Mains in Spec. Mains Stable Delay Genset On Load Generator Unload Ramp Mains In Spec and On Load Open Gen. Breaker Synchronize and Close Mains Breaker Mains in Spec. Gen Breaker Closes To Dead Bus Gen Stable. Start Fast Transfer Delay Open Mains Breaker Start Genset Mains Out of Spec* TIME Fast Transfer Delay VIS-111 00-04-27 *Over/Under Frequency and/or Over/Under Voltage Figure 5-6. Generator Off Line Woodward 133