Download EGCP-2 Engine Generator Control Package
Transcript
EGCP-2 Engine Generator Control Package Manual 26174 Real Load Control Problem kW for a phase(s) reads negative. Probable Cause Current transformer(CT) has reversed polarity Unit carries improper proportion of real load during isochronous load sharing Rated KW set point in configuration menu set at incorrect value A proportional dc speed error exists on the speed control unit (no-load speed not set to match bus frequency) Real load control is unstable when paralleled with the mains source Real load control dynamics in real load control menu are improperly set up Process control operation causes overload or reverse power PROCESS ACTION set point in process control menu set for incorrect action Loading and/or unloading is too fast/slow Load and/or unload ramp rates in the real load control menu are set incorrectly Engine speed/load has an instability that fluctuates very quickly. Speed control dynamics are improperly set up 162 Corrective Action Verify/reverse polarity of current transformer for effected channel(s) NOTE: engine generator set must be off to safely open circuit a current transformer. Appropriately set Rated KW set point in configuration menu. See description of set points. Adjust speed setting of speed control to match the bus frequency. If unit is carrying too little load, the speed setting needs increased. If unit is carrying too much load, the speed setting needs decreased. Tune Real load control dynamics in real load control menu. See description of set points. Appropriately set PROCESS ACTION set point in process control menu. See description of set points. Appropriately increase/decrease the Load and/or unload ramp rates in the real load control menu. See description of set points. Tune the speed control dynamics for stable operation. See speed control manufacturer’s instruction manual for more details. Woodward