Chapter 8. RESTRICTIONS AND IMPORTANT NOTES ON USE
■■ Prohibited Usage of Compressed Folders
Do not use Windows folder compression. It is possible that loader operations will
result in an error.
■■ List of Value Limits
Data
Project name and mapping name
Unit
Characters
Limit
Not exceeding 20 characters
Subsystem name, node name, and Bytes
chain name
Not exceeding 16 bytes
Comments
Characters
255 characters
Chain ID, subsystem ID, and node
ID
Range
1 - 65535
No. of project modules
No. of modules
31 or less
No. of workgroup modules
No. of modules
31 or less
No. of simultaneous trend monitor
data packets
Data packets
256 or less
1 logging file and No. of image
samples (No. of fixed samples)
Samples
100 to 60000 or less *1
Monitor cycle
Milliseconds
400 msec or more *2
Minimum communication interval
Milliseconds
0-1000 *3
Timeout
Milliseconds
10-10000 *3
No. of resend times
No. of times
0-10 *3
Graph update cycle
n times the monitor cycle 1 or more
Alarm cycle
Milliseconds
Not less than the monitor
cycle
No. of custom monitor registrations No. of data packets
64 per grid
No. of custom trend registrations
No. of data packets
32 per group
No. of trend monitor simultaneous
displays
No. of trend groups
8
*1: Once a value has reached the upper limit, logging files are moved to a
different file and the graph display is cleared. Samples may not be created to
a maximum depending on environment factors such as the PC load and the
number of modules.
*2: Data sampling may not be performed in accordance with the monitor cycle
setting, depending on environment factors such as the PC load and the number
of modules.
The recommended monitor cycle settings for specific module numbers are
shown below.
Recommended settings:
(For Ethernet communication)
1 module
: 400 msec
2-4 modules
: 1 sec
5-16 modules
: 2 sec
17 modules or more : 4 sec
(For loader jack communication)
2000 msec
*3: These are the settings for loader communication (Ethernet and serial).
(The parameter read/write timeout values are fixed at Ethernet: 50 sec and
Serial: 40 sec)
8–2