Download Excel 10 - CentraLine
Transcript
EXCEL 10 HYDRONIC CONTROLLER SYSTEM ENGINEERING INTRODUCTION Description of Devices The zone controlled by the W7762 Controllers will typically use an Excel 10 wall module with a temperature sensor for space temperature measurement, analog setpoint input, bypass digital input push-button, and override status LED. See page 4 for form numbers of Excel 10 wall module literature for further information. The W7762A and B Controllers are two Hydronic Controllers in the Excel 10 family product line. They cover a wide range of control applications including radiators, induction units, and fan coil units with manual fan switching, and are suitable for either wall mounting or unit mounting. Heating systems can be water or electric, and cooling systems can be chilled water supply or compressors. Extensive timing and interlock features make the W7762 especially suitable for systems using electric heat and compressors. The W7762 Controllers are capable of stand-alone operation; however, optimum functional benefits are achieved when the network communication capabilities are used. The Q7750A Excel 10 Zone Manager is a communications interface that allows devices on the Excel 10 Echelon® LONWORKS® network (E-Bus) to communicate with devices on the EXCEL 5000® System C-Bus. Fig. 1 shows an overview of a typical system layout. The Q7750A also provides some control and monitoring functions. Q7752A E-BUS SERIAL ADAPTER PERSONAL COMPUTER TOOLS E-VISION C-BUS COMMUNICATION NETWORK EXCEL 10 Q7750A ZONE MANAGER EXCEL BUILDING SUPERVISOR EXCEL 500 C-BUS TO E-BUS INTERFACE DEVICE E-BUS COMMUNICATIONS NETWORK E-BUS COMMUNICATIONS NETWORK EXCEL 10 HYDRONIC CONTROLLER Q7751A E-BUS ROUTER Fig. 1. Typical system overview 3 74-2935-3r0909