EXCEL10 HYDRONIC CONTROLLER SYSTEM ENGINEERING
Table C4. Output Variables for W7762 Controllers (left).
User Address
SrcOvrdLedS
SrcHydModeS
SrcDlcShed
SrcWindowS
SrcWindowHwS
NvName
nvoHydStatus
nvoHydStatus
Engineering Units:
English (Metric) or
States plus Range
Field Name
r_o_led
mode
Digital
State
or
Value
SNVT_occupancy
OC_OCCUPIED
OC_UNOCCIPIED
OC_BYPASS
OC_STANDBY
OC_NUL
0
1
2
3
255
BYTE
CTL_COOL
CTL_HEAT
CTL_PRESSURIZE
CTL_DE_PRESSURIZE
CTL_MODE_MANUAL
CTL_MODE_FACTORY_TEST
CTL_FLOATING_OUT_SYNCH
CTL_FAN_SWITCH_OFF
CTL_START_UP_WAIT
CTL_DISABLED
0
1
2
3
4
5
6
7
8
255
nvoHydStatus
alarm_type
Same as nvoAlarm.type
nvoHydStatus
dlc_shed
Bit
NOT ACTICE
ACTIVE
0
1
Bit
CLOSED or NOT_ASSIGNED
OPEN
0
1
Bit
CLOSED or NOT_ASSIGNED
OPEN
0
1
nvoHydStatus
nvoHydStatus
eff_window_open
hw_window_open
SrcOutput1S
nvoHydStatus
output_position[0]
SNVT_lev_percent
0 to 100%
163.835% = INVALID
SrcOutput2S
nvoHydStatus
output_position[1]
SNVT_lev_percent
0 to 100%
163.835% = INVALID
SrcRmTempSptEffS
nvoHydStatus
active_set_pt
SNVT_temp_p
10 to 35°C
327.67°C = INVALID
SrcRmTempEffS
nvoHydStatus
space_temp
SNVT_temp_p
0 to 40°C
327.67°C = INVALID
SrcRestBypassTimeS
nvoHydStatus
rest_bypass_time
UWORD
0 to 65535 Min
Default
(continued)