Download Excel 10 - CentraLine
Transcript
EXCEL 10 HYDRONIC CONTROLLER SYSTEM ENGINEERING Table C2. Configuration Variables for W7762 Controllers (right). Share (SH), Map (MA), Direct Access (DA) Monitor (M), Heartbeat (HBT) SH MA DA M HBT Comments X ApplicationType identifies the current application number of the Excel 10. X VersionNo identifies the version number of the Excel 10 application. X The time stamp of the last change to the Excel 10 application configuration. Time meets the ANSI C time stamp requirement specifying the number of seconds elapsed since midnight (0:00:00), January 1, 1970. It is represented in the Intel Format and is four bytes in length. X See above. X See above. X See above. nciDeviceName contains the name of each device. This is an ASCII string with the a size of 18 characters. A name with all NULLs means that the device has not been configured. This configuration property can be used to provide more descriptive physical loacation information than can be provided by the Neuron Chip's 6 byte location string. This is the configuration property used to control the maximum time that expires before the node object automatically transmits nvoStatus. This provides a heartbeat output that can be used by the destination objects to ensure that the node is still healthy. The heartbeat output may be disabled by setting nciMaxSendTime = 0. This is the configuration property used to control the maximum time that elapses after the last update to • • • • • • • • • nviApplicMode nviDlcShed nviWindow nviManCool nviManHeat nviSensorOcc nviSetPtOffset nviSpaceTemp nviTodEvent before these NV inputs adopt their default values. Setting nciRcvHrtBt = 0 means, that the assigned NV input does not wait for an periodic update, and that it will never revert to any default when not receiving an update. If nviSpaceTemp and nviApplicMode are not received at regular intervals that are less than the heartbeat time, the controller will assume that there is a communication failure and revert to Occupied mode. This is the configuration property used to control the maximum time that expires before the object automatically transmits the current value of • • • • • • • • • • • nvoActiveSetPt nvoAlarm nvoApplicMode nvoCoolOutput nvoWindow nvoHeatOutput nvoHydStatus nvoSensorOcc nvoSpaceTemp nvoTerminalLoad nvoUnitStatus This provides a heartbeat output that can be used by the destination objects to ensure that the node is still healthy. The heartbeat output may be disabled by setting nciSndHrtBt = 0. (continued) 39 74-2935-3r0909