7.9
Settings
For a complete set-up of the system settings must be made. These can be
made/parameterised via the operating and display panel of the AS-i controllerE.
The following settings can be made:
•
Module type AS-EP or AS-EP4 (1 or 2 limit switches per fire damper)
•
Contact assignment of AS-EP/AS-EP4 as NC or NO contacts
•
Text selection for AS-EP4: CLOSED, NOT CLOSED or NOT OPEN, OPEN
•
Sequential interlocking ON/OFF
•
Control via a relay contact ON/OFF
•
Maintenance run 1, close or open again the fire damper in case of an error
•
Maintenance run 2, maintain all dampers successively or at the same time
•
Manual operation ON/OFF
•
Activate/deactivate smoke detector
For further general details concerning the functionalities assigned to the settings see
chapter 5 of this manual.
For further details concerning settings via the UserMenu (operating and display panel
of the AS-i controllerE) please refer to chapter 6.10 of this manual.