Download Operating instructions

Transcript
Appendix
KBR multicomp 5D6
8.5.6 Electrical connection
Connection
elements
Plug terminals
Permissible
cross section of
connection lines
2.5 mm2
Measuring voltage
inputs
Fuse protection
max. 6 A
Measuring current
inputs
Fuse protection
NONE!!! Always short-circuit current
transformer terminals k and l prior to
opening the circuit!
Input
control voltage
Module bus
connection
8.5.7 Connection material
ready-made KBR system cable (6 pole
modular cable, unshielded), max.
length 30m if placed accordingly
Mechanical data
Housing measurements
90 x 71 x 61 mm (H x W x D)
Mounting type
Wall mounting on DIN rail 7.5mm deep,
in accordance with DIN EN 50022
Suitable for distribution board
mounting
Weight
approx. 175g
EDEBDA0204-4514-1_EN
Busbar
devices
via measuring voltage
102
V5.00