Section 10-4
Torque Limits
Positioning that Does Not Reach Target Position (Example: Pushing a Load)
ABSOLUTE MOVEMENT
(word a, bit 03)
Forward Rotation Current
Limit Designation Bit (word
a+16, bit 14)
When position deviation has accumulated due to pushing,
torque in the pushing direction that is greater than the limit
value will be generated if the forward rotation current limit is
cleared, which may result in damage to the device.
Therefore, specify a torque limit in the pushing direction also
when starting operation in the opposite direction.
When positioning is not
completed and the position
deviation due to pushing
remains, the axis's Busy
Flag will remain ON until
DECELERATION STOP or
This flag remains ON for the time the output torque is limited by the limit value.
other stop operation is
executed.
Receiving Command Flag
(word b, bit 00)
Busy Flag (word b, bit 13)
Torque Limit Status Flag
(word b+1, bit 09)
Position
Pushing direction target
position (position command
value)
Solid line: Command present position
Pushing stop position
Broken line: Feedback present position
(Servomotor's actual position)
Speed
Time
Solid line: Command speed
Pushing direction target
speed (speed command
value)
Time
Broken line: Servomotor's actual speed
Position deviation
Start
Pushing
Start in opposite
direction
Time
Time in which accumulated position deviation is consumed
a = Beginning word of Axis Operating Output Areas specified in Common Parameters + (Axis No. −1) × 25
b = Beginning word of Axis Operating Input Areas specified in Common Parameters + (Axis No. −1) × 25
Note
362
In applications such as pushing a load, when using the torque limit function to
limit the output torque of the Servomotor and stop the machine, the command
present position reaches the target position while the feedback present position does not, which causes the pulses to accumulate for the position deviation in the Servo Drive’s deviation counter. To change movement to the
opposite direction, send the operating command with the Current Limit Designation Bit setting enabled in the pushing direction.
If the Current Limit Designation Bit setting is disabled for the direction in which
the load is being pushed when operation is started in the opposite direction
(i.e., an operating command is sent without specifying the torque limit), torque
will be generated in the pushing direction at the start of operation. This is due
to the position deviation accumulated in the pushing direction and may result
in damage to the machine or an accident.