Download M57x Bitronics Compact IED ref: M57x_EN_M_E

Transcript
User Manual
M57x/EN M/E
M57x
Page 39
Filename
Directory
Description
COMM.INI
c:\CONFIG\
Contains serial port information.
DEMANDS.INI
c:\CONFIG\
Contains demand intervals.
DIO.INI
c:\CONFIG\
Contains Digital I/O data, i.e. the Digital I/O debounce time.
c:\CONFIG\
Contains setup information for communicating with a remote
display
DNP.BIN
c:\CONFIG\
Contains DNP configurable register information
DR1.INI
c:\CONFIG\
Contains setup information for Disturbance Recorder 1
DR2.INI
c:\CONFIG\
Contains setup information for Disturbance Recorder 2
c:\CONFIG\
Contains CT/VT ratios, user gains and phase, harmonic
denominators, and VA calculation types.
c:\CONFIG\
Contains Identity info, i.e. device name of M57x, IP address,
NSAP address.
c:\CONFIG\
Contains Modbus configurable register information
c:\CONFIG\
Contains Modbus, Modbus Plus, and DNP protocol setup
information.
SBO.INI
c:\CONFIG\
Contains UCA2.0 Select Before Operate parameters
SCALEFAC.INI
c:\CONFIG\
Contains integer-to-floating point scale factor info for UCA.
TR1.INI
c:\CONFIG\
Contains setup information for TR1 recorder.
VIO.INI
c:\CONFIG\
Contains Virtual Input/Output setting information.
WR1.INI
c:\CONFIG\
Contains Waveform Recorder 1 Configurator parameters
WR2.INI
c:\CONFIG\
Contains Waveform Recorder 2 Configurator parameters
TRIGGER.INI
c:\CONFIG\
Contains all trigger configuration info
MEASUSER.INI
c:\CONFIG\
Contains user defined measurement names
VFT.INI
c:\CONFIG\
Contains Voltage Fluctuation Table configuration
COM.BIN
c:\PERSIST\
Password file
HARDWARE.INI
c:\CONFIG\
Contains configured hardware info
SYS_CNFG.INI
c:\PERSIST\
Contains hardware found by unit
DISPLAY.BIN
DSP.INI
IDENTITY.INI
MODBUS.BIN
PROTOCOL.INI
There are also several ".BIN" files in the "c:\CONFIG\" directory which contain information on
the protocol register configuration for Modbus, Modbus Plus and DNP. These files are
written by the 70 Series Configurator and are not editable by the user.
AFTER WRITING THE CONFIGURATION FILES, THE M57X MUST BE RESTARTED
(REBOOTED) BEFORE THE NEW CONFIGURATION WILL TAKE EFFECT.
5.3
Triggering
Triggers can be configured in the 70 Series to initiate several different actions:
Waveform Recorders
Disturbance Recorders
Digital Outputs
Virtual Outputs
SOE Entries
Resetting of various measurements (Demands, Energy, etc.)
Up to 120 triggers can be specified, of the following types: