F073 = Unit Frame Rating: Read Only. Reserved for Factory Use F074 = CT Ratio: Read Only. Primary value of the VMX Series internal Current Transformers (CTs) for use in determining the GF trip settings (F046). CTs cannot be used for external metering. Alteration is reserved for factory use only. 5.6.12.a Real Time Clock Settings Functions F075 through F080 set the system real time clock. The time clock is used in the 24hr Time Clock Controller operation (F032 – F039) and for date/time stamping of the Fault History. The clock automatically adjusts for leap years and is backed up by a Lithium ion battery for long life. Note: The time clock does not automatically adjust for daylight savings time. F075= Year Factory Setting = Year of manufacture Range = 2000 to 2047 F076 = Month Factory Setting = Month of manufacture Range = 1 – 12 F077 = Day Factory Setting = Day of manufacture Range = 1 – 31 F078 = Hour Factory Setting = Actual (EST) Range = 0 - 23 (12:00 midnight is hour 0) F079 = Minute Factory Setting = Actual (EST) Range = 0 – 59 F080 = Second Factory Setting = Actual (EST) Range = 0 – 59 F081 = Firmware revision number for Factory Use F082 -F084 = Reserved VMX Digital Solid State Soft Starter User Manual 59 | P a g e