4.11.3 Communication In Real time viewer, click on Icon Configuration data icon Click on icon to configure options, then select “Communication” tab Sampling rate: It is used to set data display time for Real-Time Viewer. User can select one from the following for real time monitoring. Time out: This is time set for generating time out errors related to real time viewer communication. For example, if IO modules and PC with data acquisition software are located at different places connected through Ethernet across different gateways, and then user can adjust sampling rate and time out settings to avoid errors in communication. When real time viewer is running, please observe the following taskbar at the bottom side of the screen. Here, scan time should always be less than sampling rate. Other wise, communication errors will occur. If PC and Modbus slave devices are connected by long distance network, then there might be chances that scan time gets increased. So check this and set sampling-rate more than scan time. Also user can set time out settings to generate communication failure errors. Maximum time out settings possible is 60 sec. For example, scan time is adjusted and time out setting = 30 sec. This means, if scan time is more than sampling rate for more than 30 sec, then communication errors will be generated. 73