Download 3.6 Terminal Description
Transcript
08- 13 08- 15 Over torque Detection Selection(OL3) 【0】:Disable Over torque Operation 【1】:Enable Over torque Operation Only if at Set Frequency 【2】:Enable Over torque Operation while the Drive is in Run Mode Operation After Over torque Detection is Activated 【0】:Coast-to-Stop After Over torque is Activated 【1】:Drive will Continue to Operate After Over torque is Activated Over torque Threshold Level Range 08- 16 【30 ~ 300】 Over torque Activation Delay Time Range 08- 17 Range 【0.0~25.0】 Fire Mode Range 08-14 Range 【0】:Disabled 【1】:Enabled ¾ Over Torque is detected when the output torque level exceeds the level set in Parameter 08-15 ( Inverter rated torque is 100%) and if it is detected for a duration of time which is set in parameter 08-16. ¾ When 08-14=【0】:If there is over torque, the inverter coasts to stop and flashes OL3. It is necessary to press’RESET’ or external terminal to continue to run. ¾ When 08-14=【1】:If there is over torque, the inverter can continue to run and flashes OL3 until the output torque is less than the 08-15 set value. ¾ Parameter 03-11/12(Multifunction output terminal) = 12, the output terminal signal will be set for over torque condition. ※ Note: Over torque detection will be enabled only when parameter 08-13 is set to options 1or2. ! warning: Fire Mode: This mode is the drive in order to ensure uninterrupted operation. This mode is set to active (08-17 = 1), most of the alarms and warnings will not cause the drive down, in order to ensure that people in the evacuation of smoke-free environment, it will extend the reliable operation of the time as much as possible until self destruction. If the drive is set to fire mode, the company for the error that occurred, failure, personal injury, or the drive itself and the other is not responsible for any loss of property. 09- Communication function group 09- 00 Assigned Communication Station Number Range ¾ 【1 ~ 32】 09-00 to set the communication station codes which are suitable for driving more than one inverters situations. 09- 01 RTU code /ASCII code Selection Range 【0】:RTU 【1】:ASCII 09- 02 Baud Rate Setting (bps) Range 【0】:4800 【1】:9600 【2】:19200 【3】:38400 09- 03 Stop Bit Selection Range 【0】:1 stop bit 【1】:2 stop bit 09- 04 Parity Selection Range 【0】:no parity 4-62