Parameters V/Hz-Characteristic Curve (P11) The M-Max series frequency inverters operate with a sinusoidal pulse width modulation (PWM) in the inverter. The IGBTs are actuated by two V/f-based control procedures that you can select in parameter P11.8. P11.8 = 0: The V/f characteristic (voltage/frequency characteristic) represents a control procedure of the frequency inverter in which the motor voltage is controlled in a specific ratio to the frequency. If the voltage/frequency ratio is constant (linear characteristic), the magnetizing flux and the torque behavior of the connected motor is virtually constant. ● Frequency control (Hz) ● Parallel connection of several motors ● Large power difference (PFU >> PMotor) In the standard application, the benchmark values for the V/Hz-characteristic curve correspond with the rated operational data of the connected motor (see the motor ratings plate): ● Switching in the output ● Cut-off frequency P11.2 = Rated motor frequency P7.6 = Maximum frequency P6.4 ● Output voltage P11.3 = Nominal motor voltage P7.5 P11.8 = 1: ● Speed control (RPM, min–1) with slip compensation ● Single operation (only one motor), maximum one power rating smaller ● High torque (requirement: exact motor data for the motor calculation model) The rating data of the V/Hz-characteristic curve is assigned automatically and corresponds with the values of parameter P7.5 (nominal motor voltage) and P7.6 (rated motor frequency). If you require other values for the V/Hz-characteristic curve, you must first set parameters P7.5 and P7.6, before you change the parameters of the V/Hz-characteristic curve shown here. V/Hz-Characteristic Curve PNU ID Access RUN Value/Range Description Factory Setting (P1.3) P11.1 108 X — V/Hz characteristic curve 0 0 Linear The output voltage changes linearly with the output frequency; from zero to voltage P11.3 with the cut-off frequency P11.2 By defining a minimum frequency (P6.3), a voltage corresponding with one of the linear characteristic curves is output The V/Hz ratio running linearly between zero and the cut-off frequency remains constant With parameter P11.6, the voltage value can be raised by percentages in a linear V/Hz-ratio over the entire manipulating range 1 Squared The output voltage changes quadratically with the output frequency; from zero to voltage P11.3 with the cut-off frequency P11.2 By defining a minimum frequency P6.3, a voltage corresponding with one of the quadratic characteristic curves is output. The V/Hz ratio running quadratically between zero and the cut-off frequency remains constant With parameter P11.6, the voltage value can be raised as a percentage by a quadratic V/Hz ratio over the entire manipulating range 2 Configurable In connection with parameters P11.4, P11.5 and P11.6, the V/Hz ratio and therefore the parameters for characteristic curve progress can be defined as required M-Max Series Adjustable Frequency Drive MN04020003E—April 2011 www.eaton.com 105