9. Communication with PLC and PWS
9.13. GE-Fanuc 90-SNP
1. The data format and range of the PLC registers which the ADP can accress :
Word Device and Bit Device.
Register Type
Format
Range with the Ragister
Data Size
Discrete Inputs
%Innnnn
nnnnn=1-12288;1 or multiple of 16+1
Word
Discrete Outputs
%Qnnnnn
nnnnn=1-12288;1 or multiple of
16+1
Word
Discrete
Temporaries
%Tnnn
nnn=1-256; 1 or multiple of 16+1
Word
Discrete Internals
%Mnnnnn
nnnnn=1-12288;1 or multiple of
16+1
Word
%SA Discretes
%SAnnn
nnn=1-128; 1 or multiple of 16+1
Word
%SB Discretes
%SBnnn
nnn=1-128; 1 or multiple of 16+1
Word
%SC Discretes
%SCnnn
nnn=1-128; 1 or multiple of 16+1
Word
%S Discretes
%Snnn
nnn=1-128; 1 or multiple of 16+1
Word
Genius Global Data
%Gnnnn
nnnn=1-7680; 1 or multiple of 16+1
Word
Registers
%Rnnnnn
nnnnn=2-16384
Word
Analog Inputs
%AInnnn
nnnn=1-8192
Word
Analog Outputs
%AQnnnn
nnnn=1-8192
Word
** The HMI can read up to 50 words in one read command.
Relay Type
Format
Range with the Relay
Discrete Inputs
%Innnnn
nnnnn=1-12288
1 or Multiple of 16+1
Discrete Outputs
%Qnnnnn
nnnnn=1-12288
1 or Multiple of 16+1
Discrete
Temporaries
%Tnnn
nnn=1-256
1 or Multiple of 16+1
Discrete Internals
%Mnnnnn
nnnnn=1-12288
1 or Multiple of 16+1
%SA Discretes
%SAnnn
nnn=1-128
1 or Multiple of 16+1
%SB Discretes
%SBnnn
nnn=1-128
1 or Multiple of 16+1
%SC Discretes
%SCnnn
nnn=1-128
1 or Multiple of 16+1
%S Discretes
%Snnn
nnn=1-128
1 or Multiple of 16+1
Genius Global Data
%Gnnnn
nnnn=1-7680
1 or Multople of 16+1
** The HMI can read up to 800 bits in one read command.
2. The illustration of the connection:
a.
PWS and RS232 of PLC miniconverter kit
420 ADP User’s Manual
Block