Download User Manual
Transcript
5.4.18 Sub-FC 67 (0x43): Set the independent/interlocked mode ‧Request Byte order Description Size Value 00 Address 1 Byte 1 ~ 247 01 FC 1 Byte 0x64 02 Sub-FC 1 Byte 0x43 03 Mode 1 Byte 0=>independent, 1=>interlocked. Byte order Description Size Value 00 Address 1 Byte 1 ~ 247 01 FC 1 Byte 0x64 02 Sub-FC 1 Byte 0x43 03 Setting result 1 Byte 0=>OK, 0xFF=>Error. ‧Response Note: 1. For the interlocked mode, please refer to Sub-FC 75 and 76 for the settings of the relay pairs. Maximum 5 relay pairs can be set. 2. For an interlocked relay pair, e.g. RL0 and RL1, three statuses are allowed: Interlocked Status Relay 0 Relay 1 1 ON (NO contact) OFF (NC contact) 2 OFF (NC contact) ON (NO contact) 3 OFF (NC contact) OFF (NC contact) IR-310-RM, IR Controlled 10-ch High Power Relay Module (Ver. 1.1, Jul/02/2013) 51